BC10 MEGA – Immersion Cooling Container

$0.00

تحديد

BASIC

PRO

Dimensions(L*W*H)(mm) 2991*2438*2591 2991*2438*2591
Shipping Weight(T) 3 3
Operating Weight(T) 6 6
Coolant Capacity (L) 3600 3600
Cycle Mode Single loop Single loop
Miner Capacity 96 S19/M50 96 S19/M50
Tank Quantity B24 Tank*4 B24 Tank*4
Operating Temperature(℃) -25°C ~55℃ -25°C ~55℃
 
Electrical Performance (- /✓ optional/standard)

BASIC

PRO

Input Voltage and Frequency 3-phase 350-480V 50/60Hz 3-phase 350-480V 50/60Hz
Max Power Load (kW) 444 706
Output Voltage and Frequency Single-phase 200-277V 50/60Hz Single-phase 200-277V 50/60Hz
Safety Certification CE/UL CE/UL
Operating Power(kW) 25 33
Power Distribution Cabinets(A) 630Ax1 *1 1000Ax1 *1
PDU Smart PDU * 4 Smart PDU * 8
Inlet Cable The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:L1 4-wires cable 1AWG(42.4mm x4) x1 *1L2 4-wires cable 1AWG(42.4mm x4) x1 *1L3 4-wires cable 1AWG(42.4mm x4) x1 *1N 4-wires cable 1AWG(42.4mm x4) x1 *1PE 1-wire cable 1AWG(42.4mm) x1 *1 The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:L1 4-wires cable 3/0AWG(85mm x4) x1 *1L2 4-wires cable 3/0AWG(85mm x4) x1 *1L3 4-wires cable 3/0AWG(85mm x4) x1 *1N 4-wires cable 3/0AWG(85mm x4) x1 *1PE 1-wire cable 3/0AWG(85mm) x1 *1
Smart Meter
Integrated Wiring
Network
UPS
SPD

Cooling Capacity

BASIC

PRO

Cooling Capacity(kW) 360 480
Cooling Type Closed water cooling tower

or Dry cooler

Closed water cooling tower

or Dry cooler

Inlet Temperature(℃) 45 45
Outlet Temperature(℃) 60 60
Design Reference Temperature (℃) 35 35

المراجعات

لا توجد مراجعات بعد.

كن أول من يقيم “BC10 MEGA – Immersion Cooling Container”

لن يتم نشر عنوان بريدك الإلكتروني. الحقول الإلزامية مشار إليها بـ *

arArabic