BC40 MEGA - Immersion Cooling Container
BC40 MEGA – Immersion Cooling Container

$0.00

BC40 MEGA – Immersion Cooling Container

$0.00

Specifications

–

BASIC

PRO

Dimensions(L*W*H)(mm) 12192*2438*2896 12192*2438*2896
Shipping Weight(T) 13 13
Operating Weight(T) 23 23
Coolant Capacity (L) 14000 14000
Cycle Mode Single loop Single loop
Miner Capacity 384 S19/M50 384 S19/M50
Tank Quantity B24 Tank*16 B24 Tank*16
Operating Temperature(℃) -25°C ~55℃ -25°C ~55℃
 
Electrical Performance (- /✓ optional/standard)
–

BASIC

PRO

Input Voltage and Frequency 3-phase 350-480V 50/60Hz 3-phase 350-480V 50/60Hz
Max Power Load (kW) 1693 2822
Output Voltage and Frequency Single-phase 200-277V 50/60Hz Single-phase 200-277V 50/60Hz
Safety Certification CE/UL CE/UL
Operating Power(kW) 100 134
Power Distribution Cabinets(A) 1200Ax1 *2 1000Ax2 *2
PDU Smart PDU * 16 Smart PDU * 32
Inlet Cable The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:L1 4-wires cable 3/0AWG(85mm x4) x1 *2L2 4-wires cable 3/0AWG(85mm x4) x1 *2L3 4-wires cable 3/0AWG(85mm x4) x1 *2N 4-wires cable 3/0AWG(85mm x4) x1 *2PE 1-wire cable 3/0AWG(85mm) x1 *2 The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:L1 4-wires cable 3/0AWG(85mm x4) x2 *2L2 4-wires cable 3/0AWG(85mm x4) x2 *2L3 4-wires cable 3/0AWG(85mm x4) x2 *2N 4-wires cable 3/0AWG(85mm x4) x2 *2PE 1-wire cable 3/0AWG(85mm) x2 *2
Smart Meter – ✓
Integrated Wiring ✓ ✓
Network ✓ ✓
UPS – –
SPD ✓ ✓

Cooling Capacity

–

BASIC

PRO

Cooling Capacity(kW) 1440 1920
Cooling Type Closed water cooling tower

or Dry cooler

Closed water cooling tower

or Dry cooler

Inlet Temperature(℃) 45 45
Outlet Temperature(℃) 60 60
Design Reference Temperature (℃) 35 35

Reviews

There are no reviews yet.

Be the first to review “BC40 MEGA – Immersion Cooling Container”

Your email address will not be published. Required fields are marked *

en_USEnglish